If you can’t find what you’re looking for, please give us a call at 888-855-8880

CN7232

“Advanced Garage Ventilation Controller For Demand Controlled Ventilation Using: Carbon Monoxide (Gas Vehicles),
Nitrogen Dioxide (Diesel), Combustible Gases (Alternative Fuels), Carbon Dioxide (Any Combustion Source)”

Description

Key Features:

  • A versatile PLC based controller that utilizes AirTest proven sequence of operation to maximize energy
    savings and ensure exceptional garage air quality. The version that works with variable speed drives
    consistently achieves fan energy savings in excess of 90%.
  • The keypad on the controller provides status indication of sensor readings and the control output
    and also includes a number of user adjustable parameters including:
    • Time Adjustment

    • 7 day occupancy programming
    • Adjustment of VFD operational parameters
    • Adjustment of of high level averaging period with drives control
    • Settings for high alarm indication and off dead-band
    • Designed to sound alarm on high levels and activate a strobe on a sensor malfunction.
    • Horn And strobe silence
  • Can be ordered for single gas control (CO) or multiple gas control (CO, NO2)
  • Can be configured to take input from 4 to 32 sensors.
  • System provides power to the sensors.
  • UL50 Rated enclosure.
  • Standard version provides 2, 4-20 Ma VFD signals, options for additional outputs available.
  • Keypad mounted outside the controller.
Typical Applications

  • Enclosed vehicle facility ventilation control for garages 42,000 to 250,000 sq ft.
  • Proven energy reduction (kWh) of 95% peak energy reduction of 95%
  • Designed to work with VFD controlled fans but can provide on/off or staged ventilation control.
  • Multiple zone capability (up to 6).
  • Works with AirTest 4-20 mA gas transmitters (TR2000-CO and TR3210-NO2).
  • CO only or CO and NO2 configuration.

Accessories

  • Horn and strobe components available in 110VAC or 24VAC.
  • Phone dialler on system alarm.
  • AirTest offers very competitive pricing on Danfoss VFDs that incorporate a energy meter, allowing tracking of ongoing energy savings of the system. Please ask us for a quote.
  • Enclosure lock.
  • Temp Range: -30 to 140°F (-40 to 60°C)
  • Power options: 115 VAC, 220 VAC
  • Enclosure size 20"(H) X 16"(W) X 6" (D)
  • Two 4-20mA outputs for VFD control. Option for more outputs available
  • Three 5A relays: 1) High Level Alarm, 2) Controller/Sensor Fault, 3) Factory Configurable
  • Keypad indicates controller status and allows for adjustment of major operating parameters.

Downloads

DATASHEET
CN7232
(1.97 MB)